20'-0" × 14'-0" · Corrugated Metal Roof · No Walls
Scale: NTS (Not To Scale)
Date: Feb 2026
Owner-Builder Project
Citrus County, FL
Plan View (Top) — Looking Down
Front Elevation — 9'-0" Open Side
Side Elevation — Showing Roof Slope (9' Front → 8' Back)
Connection Detail & Post Footing
Legend
4x6 PT Posts (8)
2x8 Beams (2 × 20')
2x6 Rafters / Knee Braces
26ga Corrugated Metal Roof
Gutter + 50gal Water Tank
Quikrete Concrete Footing
Hurricane Straps (H2.5A)
Open Area (No Walls)
STRUCTURAL NOTES: All lumber to be #2 or better Southern Yellow Pine (SYP). All posts to be Pressure Treated (PT) rated for ground contact (UC4B minimum).
Posts buried 3'-0" min with Quikrete Fast-Set footing, 12" diameter hole recommended.
Hurricane straps (Simpson H2.5A or equiv.) at every rafter-to-beam connection.
Knee bracing required at all 8 posts — 45° angle, 2x6 minimum, ~4' length each side.
Corrugated metal roof: 26 gauge min, panels overlapped 1 corrugation, fastened with #12 hex-head roofing screws with neoprene washers at 12" OC on edges, 24" OC field.
Gutter on low (rear) side; first-flush diverter recommended before 50-gal collection tank.
Verify setbacks and obtain Citrus County permit before construction. Call (352) 527-5310.